The usual pretreatment system for RO system consists of the following process: 


Coarse filtration (~80 microns) to remove large particles, adding sodium hypochlorite and other oxidants, and then precision filtration through a multi-media filter or clarifier, and then adding sodium bisulfite to reduce residual chlorine and other oxidants. Finally, install a security filter before the inlet of the high-pressure pump. 


The role of the security filter is as the name suggests. It is used as the ultimate insurance measure to prevent accidental large particles from damaging the impeller and membrane elements of the high-pressure pump. Water sources with more suspended particles usually require a higher degree of pretreatment to meet the specified water inlet requirements; for water sources with high hardness content, it is recommended to use softening or adding acid and adding scale inhibitors, etc., for the content of microorganisms and organic matter High water sources also require the use of activated carbon or anti-pollution membrane elements.